Yaskawa D1000 Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Yaskawa D1000 series power regenerative converter unit. Search or filter through the complete diagnostic directory below.
Power Range
5 – 630 kW (3-Phase)
Supply Voltage
200–240V / 380–480V AC
Control Method
Sine-Wave PWM Control
Operator Interface
5-Line LCD / LED Keypad
Complete Yaskawa D1000 Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type oC, ov, Uv1, or Overheat).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Aov Power Supply Overvoltage | Cause: The input power supply voltage is too high. Remedy: Reduce the voltage to within the range in the power supply specifications. |
| AUv Power Supply Undervoltage | Cause:
Remedy:
|
| bUS Option Communication Error | Cause:
Remedy:
|
| CE MEMOBUS/Modbus Communication Error | Cause: Faulty communications wiring or an existing short circuit. Remedy:
|
| CoF Current Offset Fault | Cause: An error occurred in the power supply detection circuit (automatic current offset adjustment failed). Remedy: Cycle the power supply and check operation. If the fault occurs again, replace the board or converter. |
| CPF00, CPF01, CPF11 to CPF22, CPF26 to CPF35 Control Circuit Error | Cause:
Remedy:
|
| CPF02 A/D Conversion Error | Cause: Control circuit is damaged (A/D conversion error). Remedy: Cycle power to the converter. If the problem continues, replace the control board or the entire converter. |
| CPF03 Control Board Connection Error | Cause:
Remedy:
|
| CPF06 EEPROM Memory Data Error | Cause:
Remedy:
|
| CPF07, CPF08 Terminal Board Connection Error | Cause: There is a faulty connection between the terminal board and the control board. Remedy: Turn off the power and reconnect the terminal board. If the problem continues, replace the control board or the entire converter. |
| CPF23 Control Board Connection Error | Cause: Hardware is damaged. Remedy: Turn off the power and check the connection between the control board and the converter. If the problem continues, replace the control board or the entire converter. |
| CPF24 Unit Capacity Detect Fault | Cause: Hardware is damaged (converter capacity cannot be detected). Remedy: If the problem continues, replace the control board or the entire converter. |
| E5 MECHATROLINK Watchdog Timer Error | Cause: Data has not been received from the PLC (watchdog timed out). Remedy: Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and proceed to phase 3. Refer to the MECHATROLINK Option Technical Manual. |
| EF0 Option Card External Fault | Cause:
Remedy:
|
| EF1 to EF8 External Fault (Input terminals S1 to S8) | Cause:
Remedy:
|
| Err EEPROM Write Error | Cause:
Remedy:
|
| Fan Internal Fan Fault | Cause:
Remedy:
|
| Fdv Power Supply Frequency Fault | Cause:
Remedy:
|
| FUA AC Fuse Blowout The power supply fuse is open. | Cause: The power supply fuse is open. Remedy:
|
| FUd DC Fuse Blowout The DC converter output fuse is open. | Cause: The main transistor failed. The DC circuit fuse is open. The drive failed. Remedy:
|
| GF Ground Fault Current exceeded Ground Short Detection Level at power supply side. | Cause: A damaged cable is creating a short circuit. Excessive leakage current at the drive output. Hardware problem. Wiring of detection circuits (r1, ℓ1, t1) or main circuits is incorrect. Remedy:
|
| nSE Node Setup Error A terminal assigned to node setup closed during run. | Cause: The node setup terminal closed during run. A Run command was issued while the node setup function was active. Remedy:
|
| oC Overcurrent Output current greater than specified level. | Cause: A momentary power loss occurred. One of the cables has shorted out or there is a grounding problem. The load is too heavy. Remedy:
|
| oFA00 Option Card Connection Error (CN5-A) Option compatibility error. | Cause: The option card installed into port CN5-A is incompatible with the converter. Remedy:
|
| oFA01 Option Card Fault (CN5-A) Option not properly connected. | Cause: The option card connection to port CN5-A is faulty. Remedy:
|
| oFA05 to oFA06 oFA10 to oFA11 oFA12 to oFA17 oFA30 to oFA43 Option Card Error (CN5-A) | Cause: Option card or hardware is damaged. Communication Option Card Connection Error (CN5-A). Remedy:
|
| oFb00 Option Card Fault (CN5-B) Option compatibility error. | Cause: The option card installed into port CN5-B is incompatible with the converter. Remedy:
|
| oFb01 Option Card Fault (CN5-B) Option not properly connected. | Cause: The option card connection to port CN5-B is faulty. Remedy:
|
| oFb02 Option Card Fault (CN5-B) Same type of option card is currently connected. | Cause: An option card of the same type is already installed in option port CN5-A. Remedy:
|
| oFb03 to oFb11 oFb12 to oFb17 Option card error (CN5-B) | Cause: Option card or hardware is damaged. There is a fault in the option card. Remedy:
|
| oFC00 Option Card Connection Error (CN5-C) Option compatibility error. | Cause: The option card installed into port CN5-C is incompatible with the converter. Remedy:
|
| oFC01 Option Card Fault (CN5-C) Option not properly connected. | Cause: The option card connection to port CN5-C is faulty. Remedy:
|
| oFC02 Option Card Fault (CN5-C) Same type of option card is currently connected. | Cause: An option card of the same type is already installed in option port CN5-A or CN5-B. Remedy:
|
| oFC03 to oFC11 oFC12 to oFC17 Option Card Error (CN5-C) | Cause: Option card or hardware is damaged. There is a fault in the option card. Remedy:
|
| oFC50 to oFC55 Option Card Error (CN5-C) | Cause: Option card or hardware is damaged. Remedy:
|
| oH Heatsink Overheat Temperature exceeded pre-alarm level (L8-02). | Cause: Surrounding temperature is too high. Load is too heavy. Internal cooling fan is stopped. Remedy:
|
| oH1 Overheat 1 Heatsink temperature exceeded converter overheat level. | Cause: Surrounding temperature is too high. Load is too heavy. Internal cooling fan is stopped. Remedy:
|
| oL2 Converter Overload Thermal sensor triggered overload protection. | Cause: Load is too heavy. Converter capacity is too small. The converter does not operate. Remedy:
|
oPr External Digital Operator Connection Fault The external operator has been disconnected from the converter. | Cause: External operator is not properly connected to the converter. Remedy:
|
ov Overvoltage Voltage in the DC bus has exceeded the overvoltage detection level. (200 V Class: ~410 V, 400 V Class: ~820 V) | Cause:
Remedy:
|
PF2 Input Power Supply Fault Abnormal oscillation in the main circuit DC bus continued. | Cause:
Remedy:
|
PF3 Input Phase Loss Detection The voltage balance in the three-phase power supply has broken down. | Cause:
Remedy:
|
SC Input Short-circuit / Main Transistor Failure Short circuit or ground fault is detected. (Note: Fault reset signals are not accepted to prevent accidents). | Cause:
Remedy:
|
SrC Phase Order Fault The phase order detection direction for the input power supply changed after the power supply was turned on. | Cause:
Remedy:
|
Uv1 Main Circuit Undervoltage The main circuit DC voltage became equal to or lower than the set value (200 V: ~190V, 400 V: ~380V). | Cause:
Remedy:
|
Uv2 Control Power Supply Voltage Fault Voltage is too low for the control converter input power. | Cause: Internal circuitry is damaged. Remedy:
|
Uv3 Undervoltage 3 (Soft-Charge Bypass Circuit Fault) The soft-charge bypass circuit failed. | Cause: The relay or contactor on the soft-charge bypass circuit is damaged. Remedy:
|
Uv4 Gate Drive Board Undervoltage Voltage drop in the gate drive board circuit. | Cause: Not enough power is being supplied to the gate drive board. Remedy:
|
vrE Resonance Detection A filter resonance fault was detected or there is a harmonic component on the power supply side. | Cause:
Remedy:
|
| AEr Communication Option Station Number Setting Error | Cause: Station number is set outside the possible setting range. Remedy:
|
| Aov Power Supply Overvoltage | Cause: The input power supply voltage is too high. Remedy:
|
| AUv Power Supply Undervoltage | Cause: The power supply voltage is low, a phase loss occurred, or voltage detection failed. Remedy:
|
| bb Baseblock | Cause: External baseblock signal was entered via one of the multi-function input terminals (S1 to S8). Remedy:
|
| bUS Option Communication Error | Cause: Connection broken, option damaged, improper connection, or data error due to noise. Remedy:
|
| CALL Serial Communication Transmission Error | Cause: Communications wiring is faulty, programming error on master side, circuitry damaged, or termination resistor setting incorrect. Remedy:
|
| CE MEMOBUS/Modbus Communication Error | Cause: Data error due to noise, incompatible protocol, CE detection time (H5-09) set too short, PLC hardware/software problem, or cable disconnected. Remedy:
|
| CoF Current Offset Fault | Cause: A fault occurred in the current detection circuit. Remedy:
|
| CrST Cannot Reset | Cause: Fault reset was being executed when a Run command was entered. Remedy:
|
| CyC MECHATROLINK Communications Cycle Setting Error | Cause: The communications cycle of the MECHATROLINK option card is out of range. Remedy:
|
| E5 MECHATROLINK Watchdog Timer Error | Cause: There is no continuity in the watchdog timer in the data that is sent by the host controller. Remedy:
|
| EF0 Option Card External Fault | Cause: An external fault was received from the PLC (with F6-03 set to 3), or there is a problem with the PLC program. Remedy:
|
| EF1 External Fault (Input Terminal S1) | Cause: An external device has tripped an alarm function, wiring is incorrect, or multi-function contact inputs are set incorrectly. Remedy:
|
| EF2 External Fault (Input Terminal S2) | Cause: External fault at multi-function input terminal S2. Remedy:
|
| EF3 External Fault (Input Terminal S3) | Cause: External fault at multi-function input terminal S3. Remedy:
|
| EF4 External Fault (Input Terminal S4) | Cause: External fault at multi-function input terminal S4. Remedy:
|
| EF5 External Fault (Input Terminal S5) | Cause: External fault at multi-function input terminal S5. Remedy:
|
| EF6 External Fault (Input Terminal S6) | Cause: External fault at multi-function input terminal S6. Remedy:
|
| EF7 External Fault (Input Terminal S7) | Cause: External fault at multi-function input terminal S7. Remedy:
|
| EF8 External Fault (Input Terminal S8) | Cause: External fault at multi-function input terminal S8. Remedy:
|
| Fan Converter Internal Circulation Fan Fault | Cause: An internal circulation fan or MC power supply is faulty (2A0130 or 4A0130 to 4A0370). Remedy:
|
| Fdv Power Supply Frequency Fault | Cause:
Remedy:
|
| HCA Current Alarm | Cause: Load is too heavy (Current exceeded 150% of rated current). Remedy:
|
| LT-1 Cooling Fan Maintenance Time | Cause: The cooling fan has reached 90% of its expected performance life. Remedy:
|
| LT-2 Capacitor Maintenance Time | Cause: The main circuit and control circuit capacitors have reached 90% of their expected performance lives. Remedy:
|
| LT-3 Soft Charge Bypass Relay Maintenance Time | Cause: The DC bus soft charge relay has reached 90% of expected performance life. Remedy:
|
| oH Heatsink Overheat | Cause:
Remedy:
|
| oL2 Converter Overload | Cause:
Remedy:
|
| ov DC Bus Overvoltage | Cause:
Remedy:
|
| PAUv Power Supply Undervoltage Pre-Alarm | Cause:
Remedy:
|
| PF3 Input Phase Loss Detection | Cause:
Remedy:
|
| SE MEMOBUS/Modbus Test Mode Fault | Cause: A fault occurred during MEMOBUS/Modbus Communications Test Mode. Remedy:
|
| SrC Phase Order Fault | Cause:
Remedy:
|
| Uv Undervoltage | Cause:
Remedy:
|
| vrE Resonance Detection | Cause: There is noise on the power supply line. Remedy:
|
Err EEPROM Write Error A verification mismatch occurred when writing data to the EEPROM. | Cause: 1. The data was corrupted by noise when writing data to the EEPROM. 2. EEPROM Hardware Failure. Remedy:
|
oPE01 Converter Capacity Setting Fault Converter capacity and the value set to o2-04 do not match. | Cause: The drive model selection (o2-04) and the actual capacity of the converter are not the same. Remedy: Correct the value set to o2-04. |
oPE02 Parameter Range Setting Error Use U1-18 to find parameters set outside the range. | Cause: Parameters were set outside the possible setting range. Remedy: Set parameters to the proper values. Note: When multiple errors occur simultaneously, other errors are given precedence over oPE02. |
oPE03 Multi-Function Input Selection Error A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-08. | Cause: The same function is assigned to two multi-function inputs. Excludes “Not used” and “External Fault.” Remedy:
|
oPE04 Terminal Board Mismatch Error The converter or the removable terminal block with parameter backup was replaced. | Cause: The converter was replaced (but the removable terminal block with parameter backup was not replaced), OR the removable terminal block was replaced. Remedy:
|
oPE05 Run Command Selection Error The settings for the Run Command or Bus Voltage Command are not correct. | Cause: The Run command is assigned to an option card (b1-18 = 3 or b1-02 = 3) and an input option card is not connected to the converter. Remedy: Reconnect the input option card to the converter. |
oPE07 Multi-Function Analog Input Selection Error A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06. | Cause: At least two of these parameters have the same setting: H3-02, H3-10, or H3-06. Remedy: Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict. |
oPE30 Incorrect Input Voltage Adjustment The input voltage offset adjustment has not been performed. | Cause:
Remedy: For information on clearing the fault, consult with your Yaskawa representative or the nearest Yaskawa sales office. |
| CoPy Writing Parameter Settings (flashing) | Cause: The operator is currently writing parameter settings to the converter. Remedy: Status display only. Wait for the task to complete. |
| CPyE Error Writing Data | Cause: An error occurred while attempting to write data to the converter. Remedy: Press any key on the operator to clear the error. Check connections and compatibility. |
| CSEr Copy Unit Error | Cause: A hardware or data error occurred within the Copy Unit. Remedy: Press any key on the operator to clear the error. If the problem persists, replace the Copy Unit. |
| dFPS Model Mismatch | Cause: The model number of the drive does not match the data being copied. Remedy: Press any key on the operator to clear the error. Ensure the source and target drive models match. |
| End Task Complete | Cause: The requested copy/verify task has finished successfully. Remedy: Status display only. No action required. |
| iFEr Communication Error | Cause: Data communication between the operator/copy unit and the converter was interrupted. Remedy: Press any key to clear. Check the cable connection between the operator and the converter. |
| ndAT Model, Voltage Class, Capacity Mismatch | Cause: The model, voltage class, or capacity specifications do not match between the saved data and the converter. Remedy: Press any key to clear. Parameters can only be saved when voltage class, capacity, control mode, and software version match (See Note 3). |
| rdEr Error Reading Data | Cause: An error occurred while reading data from the converter. Remedy: Press any key to clear the error. Retry the read operation. |
| rEAd Reading Parameter Settings (flashing) | Cause: The operator is currently reading parameter settings from the converter. Remedy: Status display only. Wait for the task to complete. |
| vAEr Voltage Class, Capacity Mismatch | Cause: The voltage class or capacity of the converter does not match the data in the copy unit. Remedy: Press any key to clear. Verify the converter rating plate matches the intended configuration. |
| vFyE Parameter Mismatch | Cause: Parameter settings in the converter and those saved to the copy function are not the same. Remedy: Press any key to clear. Review parameters to identify differences. |
| vrFy Comparing Parameter Settings (flashing) | Cause: The system is currently comparing the parameters in the converter with the saved data. Remedy: Status display only. Wait for the task to complete. |
How to Clear & Reset Yaskawa D1000 Faults
- Keypad Reset: Press the red RESET button on the digital operator keypad while the fault display is visible. Make sure to clear or remove the active Run command signal before resetting.
- Digital Input Reset (MFDI): Close the multi-function digital input terminal programmed for Fault Reset (parameter group H1-xx = 14). Pulse the terminal from open to closed, then return to open.
- DriveWizard Plus PC Tool: Connect your PC to the converter via the USB port or copy unit interface, launch DriveWizard Plus, and issue a “Fault Reset” command directly from the status monitoring window.
- Fieldbus Control Register: Set Bit 7 (Fault Reset) from `0` to `1` in Control Command Register 0001H via embedded RS-485 Modbus RTU or optional communication modules (EtherNet/IP, Profinet, Profibus-DP).
- Power Cycle: Disconnect the main AC power line. Wait until the digital keypad completely turns off and the internal CHARGE LED indicator is fully extinguished (approx. 5 minutes for capacitor discharge), then restore mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the DC bus intermediate voltage across terminals [+1] and [-] measures strictly below 50VDC and that the internal red CHARGE indicator lamp has completely extinguished before opening terminal covers, inspecting wiring, or touching power terminals on the Yaskawa D1000 unit.