Yaskawa iQpump Micro Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Yaskawa iQpump Micro intelligent pump controller drive series. Search or filter through the complete diagnostic directory below.
Power Range
1 – 25 HP (0.75 – 18.5 kW)
Supply Voltage
200–240V / 380–480V (1-Ph / 3-Ph)
Control Modes
V/f Control (Pump Optimized)
Operator Interface
Digital HOA Keypad / LED Display
Complete Yaskawa iQpump Micro Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type oC, ov, oL1, or Dry Well).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| AJF Anti-Jam Fault | Cause: The drive was not able to clear debris from the impeller in fewer than the number of attempts set in P7-02. Remedy:
|
| bUS Option Communication Error | Cause: The connection was lost after establishing initial communication. Only detected when run command is assigned to option card. Remedy:
|
| CE MEMOBUS/Modbus Communication Error | Cause: Control data was not received for the CE detection time set to H5-09. Remedy:
|
| CPF02 A/D Conversion Error | Cause: Control circuit is damaged. Remedy:
|
| N/A Control circuit terminals shorted / Input current exceeded | Cause: Control circuit terminals have shorted out (+V, AC) or input current exceeded allowable levels. Remedy:
|
| CPF03 PWM Data Error | Cause: Hardware is damaged (Problem with PWM data). Remedy:
|
| CPF06 EEPROM Memory Data Error | Cause: Error in the data saved to EEPROM. (e.g., Power supply switched off while saving). Remedy:
|
| CPF07 Terminal Board Communications Error | Cause: There is a faulty connection between the terminal board and the control board. Remedy:
|
| CPF08 EEPROM Serial Communication Fault | Cause: Terminal board or control board is not connected properly. Remedy:
|
| CPF11 RAM Fault | Cause: Hardware is damaged. Remedy:
|
| CPF12 FLASH Memory Fault | Cause: Hardware is damaged (Problem with ROM/FLASH memory). Remedy:
|
| CPF13 Watchdog Circuit Exception | Cause: Hardware is damaged (Self-diagnostics problem). Remedy:
|
| CPF14 Control Circuit Fault | Cause: Hardware is damaged (CPU error due to noise, etc). Remedy:
|
| CPF16 Clock Fault | Cause: Hardware is damaged (Standard clock error). Remedy:
|
| CPF17 Timing Fault | Cause: Hardware is damaged (Timing error during internal process). Remedy:
|
| CPF18 Control Circuit Fault | Cause: Hardware is damaged (Non-Maskable Interrupt triggered by noise). Remedy:
|
| CPF19 Control Circuit Fault | Cause: Hardware is damaged (CPU error, manual reset due to noise). Remedy:
|
| CPF20 or CPF21 RAM/FLASH/Watchdog/Clock Error | Cause: Hardware is damaged (RAM, FLASH, Watchdog, or Clock error). Remedy:
|
| CPF22 A/D Conversion Fault | Cause: Control circuit is damaged. Remedy:
|
| CPF23 PWM Feedback Fault | Cause: Hardware is damaged. Remedy:
|
| CPF24 Drive Unit Signal Fault | Cause: Hardware is damaged (Drive capacity cannot be detected correctly). Remedy:
|
| CPF25 Terminal Board Not Connected | Cause: Terminal board is not connected correctly. Remedy:
|
| CPF26 to CPF35 CPF40 to CPF43 Control Circuit Error / CPU Error | Cause: Hardware is damaged. Remedy:
|
| E5 SI-T3 Watchdog Timer Error | Cause: Data has not been received from the PLC. Remedy:
|
| EF0 Option Card External Fault | Cause: An external fault was received from the PLC and F6-03 is set to a value other than 3. Problem with PLC program. Remedy:
|
| EF1 to EF7 Pump Fault (External Faults S1-S7) | Cause: An external device tripped an alarm function. Wiring is incorrect. Remedy:
|
| Err EEPROM Write Error | Cause: Noise has corrupted data while writing to EEPROM or Hardware problem. Remedy:
|
| FAn Internal Cooling Fan Failure | Cause: Internal cooling fan has malfunctioned. Remedy:
|
| Fdb-L PID Feedback Loss | Cause: Analog input programmed for PID feedback dropped below or rose above limits (3mA / 21mA). Remedy:
|
| GF Ground Fault | Cause: Motor insulation damaged, cable short circuit, or excessive leakage current. Remedy:
|
| Err EEPROM Write Error | Cause: Noise has corrupted data while writing to the EEPROM. Remedy:
|
| FAn Internal Cooling Fan Failure | Cause: Internal cooling fan has malfunctioned. Remedy:
|
| Fdb-L / FDBKL PID Feedback Loss | Cause: The analog input programmed for PID feedback has risen above 21 mA or fallen below 3 mA (effective only when b5-12 is set to 2). Remedy:
|
| GF Ground Fault | Cause: Motor insulation is damaged, cable is damaged causing a short, excessive leakage current, or drive started during current offset/coasting. Remedy:
|
| HFb / HFB High Feedback | Cause: The feedback signal has risen above the level set in P1-11 for the time set in P1-12. Remedy:
|
| HWL (H1H20) High Water Level | Cause: The "High Water Level" digital input is active (H1-xx = 90), or switch is programmed incorrectly. Remedy:
|
| LF Output Phase Loss | Cause: Output cable disconnected, motor winding damaged, loose terminals, motor rated current too low (<5%), or damaged transistor. Remedy:
|
| LF2 Output current imbalance | Cause: Phase loss on output side, loose terminal wires, or uneven motor impedance. Remedy:
|
| LFb / LFB Low Feedback | Cause: Feedback signal dropped below level set in P1-08 for time set in P1-09. Remedy:
|
| LoP / LOP Loss of Prime | Cause: Pump load (current/power) dropped below P1-19 level for time P1-20. Remedy:
|
| LoH20 / LWL Low Water Level | Cause: The "Low Water Level" digital input is active, switch defective, or programmed incorrectly. Remedy:
|
| n5L / MSL Net Master Lost | Cause: MEMOBUS master has been lost or timeout occurred. Remedy:
|
| not5P / NMS Not Maintaining Setpoint | Cause: Feedback deviates from setpoint > P1-15 for time P1-16. Remedy:
|
| n5E / nSE Node Setup Error | Cause: A terminal assigned to the node setup function closed during run. Remedy:
|
| oC Overcurrent | Cause: Motor overheated/insulation damaged, short circuit, heavy load, accel/decel time too short, incorrect V/f setting, or hardware issue. Remedy:
|
| oFA00 Option Card Connection Error | Cause: The option card installed into port CN5 is incompatible. Remedy:
|
| oFA01 Option Card Fault | Cause: The option card connection to port CN5 is faulty. Remedy:
|
| oFA03 to oFA43 Option Card / Comm Error | Cause: Option card or hardware is damaged. Remedy:
|
| oH Heatsink Overheat | Cause: Surrounding temperature is too high. Remedy:
Cause: Load is too heavy. Remedy:
Cause: Internal cooling fan is stopped. Remedy:
|
| oH1 Overheat 1 (Heatsink Overheat) | Cause: Surrounding temperature is too high. Remedy:
Cause: Load is too heavy. Remedy:
Cause: The internal cooling fan has reached its performance life or has malfunctioned. Remedy:
Cause: Current flowing to control circuit terminal +V exceeded the tolerance level. Remedy:
|
| oH4 Motor Overheat Fault (PTC Input) | Cause: Motor has overheated. Remedy:
|
| oL1 Motor Overload | Cause: Load is too heavy. Remedy:
Cause: Cycle times are too short during acceleration and deceleration. Remedy:
Cause: A general-purpose motor is driven below the rated speed with a high load. Remedy:
Cause: The output voltage is too high. Remedy:
Cause: The wrong motor rated current is set to E2-01. Remedy:
Cause: The base frequency is set incorrectly. Remedy:
Cause: The electrical thermal protection characteristics and motor overload characteristics do not match. Remedy:
Cause: Motor overheated by overexcitation operation. Remedy:
Cause: Parameters related to Speed Search are set incorrectly. Remedy:
Cause: Output current fluctuation due to power supply loss. Remedy:
|
| oL2 Drive Overload | Cause: Load is too heavy. Remedy:
Cause: Acceleration or deceleration time is too short. Remedy:
Cause: The output voltage is too high. Remedy:
Cause: Drive capacity is too small. Remedy:
Cause: Overload occurred when operating at low speeds. Remedy:
Cause: Excessive torque compensation. Remedy:
Cause: Parameters related to Speed Search are set incorrectly. Remedy:
Cause: Output current fluctuation due to input phase loss. Remedy:
|
| oL3 Overtorque Detection 1 | Cause: Parameter settings are not appropriate for the load. Remedy:
Cause: Fault on the machine side (e.g., machine is locked up). Remedy:
|
| oL4 Overtorque Detection 2 | Cause: Parameter settings are not appropriate for the load. Remedy:
|
| oL5 Mechanical Weakening Detection 1 | Cause: Overtorque occurred, triggering the mechanical weakening level set to L6-08. Remedy:
|
| oPr External Operator Connection Fault | Cause: External operator is not properly connected to the drive. Remedy:
|
| ou / ov Overvoltage | Cause: Deceleration time is too short and regenerative energy is flowing from the motor into the drive. Remedy:
Cause: Fast acceleration time causes the motor to overshoot the speed reference. Remedy:
Cause: Excessive braking load. Remedy:
Cause: Surge voltage entering from the drive input power. Remedy:
Cause: Ground fault in the output circuit causes the DC bus capacitor to overcharge. Remedy:
Cause: Improper parameters related to Speed Search (including Speed Search after a momentary power loss and after a fault restart). Remedy:
Cause: Drive input power voltage is too high. Remedy:
|
| PF Input Phase Loss | Cause: There is phase loss in the drive input power. Remedy:
Cause: There is loose wiring in the drive input power terminals. Remedy:
Cause: There is excessive fluctuation in the drive input power voltage. Remedy:
Cause: There is poor balance between voltage phases. Remedy:
Cause: The main circuit capacitors are worn out. Remedy:
|
| PoC Pump Over Cycle | Cause: The pump has exceeded the number of cycles set in P2-10 in the time set in P2-11 and P2-12 is set to 2 (fault). Remedy:
|
| rH Braking Resistor Overheat | Cause: Deceleration time is too short and excessive regenerative energy is flowing back into the drive. Remedy:
Cause: The duty cycle is too high. Remedy:
Cause: Excessive braking inertia. Remedy:
Cause: The braking operation duty cycle is too high. Remedy:
Cause: The proper braking resistor has not been installed. Remedy:
|
| rr Dynamic Braking Transistor | Cause: The built-in dynamic braking transistor failed. The braking transistor or the control circuit is damaged. Remedy:
|
| SC IGBT Short Circuit or Ground Fault | Cause: An IGBT fault occurred or the drive is damaged (IGBT short circuit detection circuit fault). Remedy:
|
| SEr Too Many Speed Search Restarts | Cause: The number of Speed Search restarts exceeded the value set to b3-19. Parameters related to Speed Search are set to wrong values, or the motor is coasting in the opposite direction. Remedy:
|
| TIE Time Interval Error | Cause: An error has occurred in the Real-Clock Time function of the HOA keypad. Remedy:
|
| UL3 Undertorque Detection 1 | Cause: The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable time (L6-03). Parameter settings may not be appropriate, or there is a fault on the machine side. Remedy:
|
| UL4 Undertorque Detection 2 | Cause: The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable time (L6-06). Parameter settings may not be appropriate, or there is a fault on the machine side. Remedy:
|
| UL6 Motor Underload (Underload Det 6) | Cause: The load has fallen below the underload curve defined in L6-14 for longer than the time set to L6-03. Remedy:
|
| Uv1 DC Bus Undervoltage | Cause: Voltage in the DC bus fell below detection level (L2-05). Causes include input power phase loss, loose wiring terminals, voltage problems, power interruption, worn capacitors, or damaged relay/contactor. Remedy:
|
| Uv2 Control Power Supply Voltage Fault | Cause: Voltage is too low for the control drive input power. L2-02 changed from default, wiring damaged, or internal circuitry damaged. Remedy:
|
| Uv3 Undervoltage 3 (Soft-Charge Bypass Circuit Fault) | Cause: The soft-charge bypass circuit failed (relay or contactor damaged). Remedy:
|
| VLTS Volute-Thermostat Fault | Cause: The digital input assigned to volute/thermostat (H1-0x = 88 or 89) is active, or both inputs are programmed simultaneously. Remedy:
|
| AEr Station Address Setting Error | Cause: Station number is set outside the possible setting range (CC-Link, CANopen, MECHATROLINK). Remedy:
|
| AfbL Analog Feedback Lost | Cause: Defective or broken analog input source. H3-0x is not set to B (PID Feedback). Remedy:
|
| AJA Anti-Jam Active | Cause: The drive is attempting to clear debris from the impeller. This is only effective when P7-01 (Anti-jam Operation) is set to 1. Remedy:
|
| bAT Digital Operator Battery Voltage Low | Cause: The digital operator battery is low. Remedy:
|
| bb Baseblock | Cause: External baseblock signal was entered via one of the multi-function input terminals (S1 to S7). Remedy:
|
| bUS Option Communication Error | Cause: The connection was lost after initial communication was established, or option is damaged/improperly connected. Remedy:
|
| CALL Serial Communication Transmission Error | Cause: Communications wiring is faulty, short circuit, or programming error on master side. Remedy:
|
| CE MEMOBUS/Modbus Communication Error | Cause: Control data was not received correctly for two seconds (Noise, Protocol incompatibility, or Timeout). Remedy:
|
| Clock Not Set Time and Date Not Set | Cause: Drive powered up for the first time, or button not pressed during setup screen. Remedy:
|
| CrST Cannot Reset | Cause: Fault reset was being executed when a run command was entered. Remedy:
|
| CyC MECHATROLINK Comm. Cycle Setting Error | Cause: The controller is using a comm. cycle beyond the allowable setting range. Remedy:
|
| dnE Drive Disabled | Cause: "Drive Enable" is set to a multi-function contact input (H1-xx = 6A) and the contact is open. Remedy:
|
| E5 MECHATROLINK Watchdog Timer Error | Cause: The watchdog timer expired while waiting for data from the controller. Remedy:
|
| EF Forward/Reverse Run Command Input Error | Cause: Both forward run and reverse run closed simultaneously for longer than 0.5 s. Remedy:
|
| EF0 Option Card External Fault | Cause: An external fault was received from the PLC with F6-03 set to 3. Remedy:
|
| EF1 Pump Fault (Input Terminal S1) | Cause: External device has tripped alarm or wiring incorrect on S1. Remedy:
|
| EF2 Pump Fault (Input Terminal S2) | Cause: External device has tripped alarm or wiring incorrect on S2. Remedy:
|
| EF3 Pump Fault (Input Terminal S3) | Cause: External device has tripped alarm or wiring incorrect on S3. Remedy:
|
| EF4 Pump Fault (Input Terminal S4) | Cause: External device has tripped alarm or wiring incorrect on S4. Remedy:
|
| EF5 Pump Fault (Input Terminal S5) | Cause: External device has tripped alarm or wiring incorrect on S5. Remedy:
|
| EF6 Pump Fault (Input Terminal S6) | Cause: External device has tripped alarm or wiring incorrect on S6. Remedy:
|
| EF7 Pump Fault (Input Terminal S7) | Cause: External device has tripped alarm or wiring incorrect on S7. Remedy:
|
| EoF Emergency Override Forward Run | Cause: The multi-function digital input for EmergOverrideFWD (H1-xx = AF) has been closed. Remedy:
|
| Eor Emergency Override Reverse Run | Cause: The multi-function digital input for EmergOverrideREV (H1-xx = B0) has been closed. Remedy:
|
| E5 SI-T3 Watchdog Timer Error | Cause: The watchdog timed out. Data has not been received from the PLC. Remedy:
|
| FAn Internal Cooling Fan Error | Cause: Internal cooling fan has malfunctioned. Remedy:
|
| Hbb / HbbF Safe Disable Signal Input | Cause: There is no signal at terminal H1, or the safe disable input hardware is defective. Remedy:
|
| FLGt PID Feedback Loss (Go To Freq) | Cause: PID feedback source is incorrectly installed or not working (Effective when b5-12 is 3). Remedy:
|
| Fdb-L PID Feedback Loss (Wire Break) | Cause: The analog input for PID feedback has gone above 21 mA or fallen below 3 mA. Remedy:
|
| PFrEF Minimum Pump Frequency Reference | Cause: The frequency reference is set lower than P1-06 (Minimum Pump Frequency). Remedy:
|
| PtHrt Thrust Frequency Reference | Cause: The fixed frequency reference is set to a value lower than the P4-12 (Thrust Frequency) setting. Remedy:
|
| HCA Current Alarm | Cause: Load is too heavy. Drive current exceeded overcurrent warning level (150% of rated current). Remedy:
|
| HbbF Safe Disable Signal Input | Cause: The safe disable input hardware is defective or the Safe Disable channel is broken. Remedy:
|
| FLGt PID Feedback Loss (Go To Freq) | Cause: PID feedback source is incorrectly installed or is not working. Effective only when b5-12 is set to 3. Remedy:
|
| Fdb-L PID Feedback Loss (Wire Break) | Cause: The analog input programmed for PID feedback has gone above 21 mA or fallen below 3 mA. Remedy:
|
| PFrEF Minimum Pump Frequency Reference | Cause: Drive frequency reference is set lower than P1-06 (Minimum Pump Frequency). Remedy:
|
| PtHrt Thrust Frequency Reference | Cause: The fixed frequency reference is set to a value lower than the P4-12 (Thrust Frequency) setting. Remedy:
|
| HCA Current Alarm | Cause: Drive current exceeded overcurrent warning level (150% of rated current). Load is too heavy. Remedy:
|
| H1Fb High Feedback Level Alarm | Cause: The feedback signal is too high (risen above P1-11). Remedy:
|
| LoP Loss of Prime | Cause: Water level dropped below P1-19. Could be due to dry well, air in system, or no water. Remedy:
|
| LCP Low City Pressure | Cause: Insufficient pressure is present on the inlet to the pump. Remedy:
|
| LoFb Low Feedback Level Alarm | Cause: The feedback signal is too low (dropped below P1-08). Remedy:
|
| LSP Low Suction Pressure | Cause: Insufficient suction pressure is present. Remedy:
|
| LLLt Low Water in Tank | Cause: The water level in the tank is too low. Remedy:
|
| LT-1 Cooling Fan Maintenance Time | Cause: The cooling fan has reached 90% of its expected performance life. Remedy:
|
| LT-2 Capacitor Maintenance Time | Cause: The main circuit and control circuit capacitors have reached 90% of their expected performance lives. Remedy:
|
| LT-3 Soft Charge Bypass Relay Maintenance Time | Cause: The DC bus soft charge relay has reached 90% of expected performance life. Remedy:
|
| LT-4 IGBT Maintenance Time (50%) | Cause: IGBTs have reached 50% of their expected performance life. Remedy:
|
| nEtSC NETSCAN Waiting for Master | Cause: No message was received from the master within the time set in P9-28. Remedy:
|
| notSP Not Maintaining Setpoint | Cause: The setpoint cannot be maintained (deviation > P1-15 for time P1-16). Remedy:
|
| oH Heatsink Overheat | Cause: Heatsink temperature exceeded L8-02. Cooling fan stopped. Airflow restricted. Remedy:
|
| oH2 Drive Overheat Warning | Cause: An external device triggered an overheat warning (input terminal S1-S7). Remedy:
|
| oH3 Motor Overheat | Cause: Motor thermostat wiring faulty. Machine fault. Motor overheated. Remedy:
|
| oL1 Motor Overload | Cause: Load too heavy. Cycle times too short. Wrong V/f pattern. Wrong motor rated current setting. Remedy:
|
| oL2 Drive Overload | Cause: Thermal sensor of drive triggered. Load too heavy. Accel/Decel too short. Low speed operation. Remedy:
|
| oL3 Overtorque Detection 1 | Cause: Current exceeded value in L6-02 for longer than L6-03. Remedy:
|
oL2 Drive Overload (The thermal sensor of the drive triggered overload protection) | Cause:
Remedy:
|
oL3 Overtorque Detection 1 (Current exceeded value set in L6-02 for longer than L6-03) | Cause:
Remedy:
|
oL4 Overtorque Detection 2 (Current exceeded value set in L6-05 for longer than L6-06) | Cause: Parameter settings are not appropriate for the load. Remedy: Check the settings of parameters L6-05 and L6-06. |
ov DC Bus Overvoltage (DC bus voltage exceeded the trip point) | Cause:
Remedy:
|
PCYC Pump Over Cycle | Cause: The pump has exceeded the number of cycles set in P2-10 in the time set in P2-11 and P2-12 is set to 1 (alarm). Remedy:
|
rdd Remote Drive Disable | Cause:
Remedy: Remove conditions causing the terminal to close (or open, depending on selection). |
SE MEMOBUS/Modbus Communication Test Mode Error | Cause: A digital input set to 67H (MEMOBUS/Modbus test) was closed while the drive was running. Remedy: Stop the drive and run the test again. |
TdE Time Data Error | Cause: An error has occurred in the Real-Clock Time function of the HOA keypad. Remedy: Replace the HOA keypad. Contact Yaskawa or your nearest sales representative. |
TrPC IGBT Maintenance Time (90%) | Cause: IGBTs have reached 90% of their expected performance life. Remedy: Replace the drive. |
UL3 Undertorque Detection 1 (Current fallen below L6-02 for longer than L6-03) | Cause:
Remedy:
|
UL4 Undertorque Detection 2 (Current fallen below L6-05 for longer than L6-06) | Cause:
Remedy:
|
UL6 Motor Underload (Load fallen below underload curve L6-14) | Cause: The output current has fallen below the motor underload curve defined in L6-14 for longer than the time set to L6-03. Remedy: Adjust the value set to L6-14 so that output current remains above the motor underload curve during normal operation. |
Uv Undervoltage | Cause:
Remedy:
|
| oPE01 Drive Capacity Setting Fault | Cause: The drive model selection (o2-04) and the actual capacity of the drive are not the same. Remedy:
|
| oPE02 Parameter Range Setting Error | Cause: Parameters were set outside the possible setting range. Remedy:
|
| oPE03 Multi-Function Input Selection Error | Cause: A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-07. Common conflicts include:
Remedy:
|
| oPE04 Initialization Required (Term <-> Ctrl Chg) | Cause: The drive, control board, or terminal board have been replaced and the parameter settings between the control board and the terminal board no longer match. Remedy:
|
| oPE05 Run Command/Frequency Reference Source Selection Error | Cause:
Remedy:
|
| oPE07 Multi-Function Analog Input Selection Error | Cause: A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and PID functions conflict (set to the same value). Remedy:
|
| oPE09 PID Control Selection Fault | Cause: PID control function selection is incorrect.
Remedy:
|
| oPE10 V/f Data Setting Error | Cause: V/f pattern setting error. One of the following errors occurred: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Remedy:
|
| oPE11 Carrier Frequency Setting Error | Cause: The following simultaneous contradictory settings have occurred: C6-05 > 6 and C6-04 > C6-03 (carrier frequency lower limit is greater than the upper limit). Remedy:
|
| oPE33 Net Incompatible | Cause: Parameter selection is incompatible with the selected network P9-99. Remedy:
|
| CoPy Writing Parameter Settings (flashing) | Cause: Parameters are being written to the drive. Remedy:
|
| CoPyE Error Writing Data | Cause: Failed writing parameters. Remedy:
|
| CSEr Copy Unit Error | Cause: Hardware fault. Remedy:
|
| dFPS Drive Model Mismatch | Cause: The drives used in the copy and write process are not the same model. Remedy:
|
| End Task Complete | Cause: Finished reading, writing, or verifying parameters. Remedy:
|
| iFEr Communication Error | Cause: A communication error occurred between the drive and the HOA keypad or the USB copy unit. Remedy:
|
| ndAT Model, Voltage Class, Capacity Mismatch | Cause: The drive from which the parameters were copied and the drive to which they are being written have different electrical specifications, capacities, or control modes. Remedy:
|
| rdEr Error Reading Data | Cause: Failed while attempting to read parameter settings from the drive. Remedy:
|
| rEAd Reading Parameter Settings (flashing) | Cause: Displayed while the parameter settings are being read onto the USB Copy Unit. Remedy:
|
| vAEr Voltage Class, Capacity Mismatch | Cause: The drive from which parameters were copied and the drive being verified have different specifications. Remedy:
|
| vFyE Parameter Settings Mismatch | Cause: Indicates that parameter settings that have been Read and loaded onto the Copy Unit/Keypad are different from the drive. Remedy:
|
| vrFy Comparing Parameter Settings (flashing) | Cause: The Verify mode has confirmed that parameters on the drive and copy device are identical. Remedy:
|
| CrST Cannot Reset | Cause: Fault reset was being executed when a Run command was entered. Remedy:
|
| Cur Current Limit Foldback | Cause: Displayed when drive output speed is being limited due to the output current limit. Remedy:
|
| dStGE De-staging in X sec | Cause: Displayed during multiplexing when drive de-staging is in progress. Remedy:
|
| FbcH- Feedback Drop Check | Cause: Displayed when the drive is determining whether the feedback will change abruptly when entering Sleep Mode. Remedy:
|
| LoC-P Parameter Locked | Cause: Displayed after an attempt to change a parameter when A1-01 = 3. Remedy:
|
| nEtEr Net Pump Err (Chk Faulted Pump) | Cause: Displayed when the drive has been stopped because another drive in the network has a system fault or a Low City Pressure alarm. Remedy:
|
| nEtSt Net Start Delay (P9-29 Active) | Cause: Displayed when the MEMOBUS network is waiting for the P9-29 timer to elapse. Remedy:
|
| nEtFb Network FB Lost (Check FB Source) | Cause: Displayed when no valid analog PID feedback source can be found on the network. Remedy:
|
| PASS MEMOBUS/Modbus Comm. Test Mode Complete | Cause: MEMOBUS/Modbus test has finished normally. Remedy:
|
| PrCHG Pre Chg Mode (Exit in Xsec) | Cause: Pre-charge 1 or 2 active. X indicates time left before pre-charge exits due to timers (P4-03 + P4-07). Remedy:
|
| 1PH Single Phase Foldback | Cause: Displayed when an input phase has been lost, or when excess load is being drawn by the motor in a single phase application. Remedy:
|
| SLEEP Sleep Active Wait for Start | Cause: Displayed when the drive is in Sleep Mode or waiting for the feedback level to reach the level set in P1-04. Remedy:
|
| booSt Sleep Boost Active | Cause: Displayed when the drive entering Sleep Mode and the pressure setpoint is being boosted. Remedy:
|
| StAGE Staging in X sec | Cause: Displayed during multiplexing when drive staging is in progress. Remedy:
|
How to Clear & Reset Yaskawa iQpump Micro Faults
- Keypad Reset: Press the red RESET key on the integrated HOA keypad or LED operator while the alarm code is displayed. Ensure the pump Run command (Hand/Auto) is stopped before resetting.
- Digital Input Reset (MFDI): Momentarily close the digital input terminal programmed for Fault Reset (parameter group H1-xx = 14). Pulse the terminal from open to closed, then back to open.
- DriveWizard iQpump PC Tool: Connect your computer using the USB/serial communication interface, launch DriveWizard iQpump, and click “Fault Reset” in the diagnostics monitoring window.
- MEMOBUS/Modbus Network: Set Bit 7 (Fault Reset) from `0` to `1` in Control Command Register 0001H via RS-485 Modbus serial communication.
- Power Cycle: Disconnect the incoming AC line power. Wait at least 5 minutes until the display completely goes dark and the internal CHARGE LED indicator turns off completely (allowing DC capacitors to discharge below 50VDC), then reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+1] and [-] and that the internal CHARGE LED has completely extinguished before removing protective covers, servicing pump motor leads, or touching terminals U/T1, V/T2, and W/T3 on the Yaskawa iQpump Micro drive.