Panasonic Drives Fault Codes & Troubleshooting

Complete diagnostic database for 3 Panasonic MINAS servo drive series (MINAS A5, A6, and A7). Browse alarm codes, protective functions, causes, and step-by-step fixes for high-speed AC servo motion systems. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.

3 Servo Motion Series 3 Total Series

Panasonic MINAS AC Servo Drives

3 Models

Most Common Panasonic MINAS Servo Alarm Codes

Diagnostic Quick Reference
Alarm Display Alarm Name Protective Function Common Root Cause
Err 12.0 Overcurrent Overcurrent Protection Inverter peak current limit exceeded; short circuit across motor phases U, V, W, jammed mechanical axis, or ground short.
Err 14.0 Overvoltage Main Power Overvoltage Internal DC bus voltage exceeded upper threshold; high regenerative energy returned during deceleration without regenerative resistor.
Err 13.0 / Err 13.1 Undervoltage Main Power Undervoltage Main DC bus voltage dropped below threshold; AC utility line voltage sag, open main contactor, or loose incoming terminal connections.
Err 16.0 Overload Overload Protection Continuous motor torque exceeded rated capacity according to thermal curve; mechanical binding, high friction, or undersized servo motor.
Err 15.0 Overheat Driver Overheat Protection Internal heatsink or power module temperature exceeded safety limits; clogged airflow, high control panel temperature (>55°C), or fan failure.
Err 21.0 / Err 21.1 Encoder Comms Encoder Disconnection Error Communication between drive and motor encoder disrupted; severed encoder cable, loose connector pins, or high EMI noise on feedback line.
Err 24.0 Position Error Position Deviation Excess Positional deviation counter exceeded parameter limit; servo gain too low, high mechanical load inertia, or motor stalled during positioning.

How to Clear & Reset Panasonic MINAS Alarms

  1. Front Panel Keypad: Press the SET button to enter auxiliary function mode, navigate to parameter AF_ACL (Alarm Clear), and press and hold the UP key until the display blinks to clear the active alarm.
  2. Alarm Clear Input (A-CLR): Apply a momentary 24VDC pulse to the digital input configured for Alarm Clear (default terminal A-CLR on control connector X4).
  3. PANATERM Setup Software: Connect via USB (Mini-B cable) to PC running Panasonic PANATERM, open the Alarm Monitor window, and click the “Alarm Clear” button.
  4. Main Circuit Power Cycle: Shut down both control power (L1C, L2C) and main circuit AC power (L1, L2, L3), wait until the internal CHARGE LED completely turns off, and re-energize the servo drive.
⚠️ High-Voltage Safety Warning: Hazardous electrical energy remains stored in the intermediate DC bus capacitors even after AC power has been disconnected. Wait at least 5 minutes after power shut-off and confirm that the red CHARGE indicator LED on the front face of the driver is completely unlit before inspecting terminal blocks or touching motor connections.