Delta Electronics Drives Fault Codes & Troubleshooting

Technical troubleshooting reference for Delta Electronics AC micro drives, heavy-duty industrial inverters, and ASDA high-precision servo systems. Select your drive model series below to access parameter checks, trip code descriptions, and physical inspection steps.

18 AC Inverter Series 11 ASDA Servo Series Sensored & Sensorless Vector

Delta AC Variable Frequency Drives

18 Models

Delta ASDA AC Servo Systems

11 Models

Most Common Delta Drive Fault Codes

Diagnostic Quick Reference
Trip Code Trip Name Common Physical Trigger Recommended First Check
oc / ocA Overcurrent (Accel / Steady) Excessive motor load, short acceleration ramp, or motor cable phase-to-phase short circuit. Increase acceleration time (Pr.01.12), check motor mechanical binding with shaft uncoupled.
ov / ovd DC Bus Overvoltage Regenerative energy from motor during rapid deceleration charging the internal DC bus above safety threshold. Lengthen deceleration ramp (Pr.01.13) or verify dynamic braking resistor value and wiring.
GFF Ground Fault Current leakage from output terminals (U, V, W) to protective earth exceeding 50% rated inverter current. Check for moisture inside motor conduit box or megger test motor stator insulation to earth.
oL / oL1 Motor Overload Continuous motor load drawing current above rated thermal threshold curve (electronic thermal relay tripped). Verify motor rated current setting (Pr.01.01 / Pr.05.01) and inspect machine mechanical gearbox.
oH / oH1 IGBT Overheating Heat sink temperature sensor detecting temperature exceeding allowable limits. Clean heatsink air fins, check if internal cooling fan is spinning, and inspect enclosure filters.
PHL Phase Loss Three-phase AC supply line missing one phase or severe utility phase unbalance (>3%). Measure incoming line-to-line voltages (R-S, S-T, R-T) and inspect upstream disconnect switches.
AL.001 Servo Overcurrent ASDA servo amplifier output short-circuit or damaged servo motor power harness. Inspect UVW servo cables for insulation pinch or test servo motor windings for phase shorts.

How to Clear & Reset Delta VFD Faults

  1. Keypad Reset: Press the red RESET button on the digital keypad (or press STOP/RESET on MS300/C2000 models).
  2. External Terminal Pulse: If hardwired, close the multi-function input terminal programmed as “Fault Reset” (default setting `05` on terminals MI1–MI8).
  3. Communication Reset: Write control word `0002H` to Modbus communication address `2000H` via RS-485 / Modbus serial link.
  4. Power Cycle: Turn off main power supply, wait until the digital keypad screen completely turns off (DC bus discharged), then switch power back on.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus capacitor voltage measures strictly below 50VDC between terminals (+/B1 and -) before opening enclosure covers or inspecting terminals U, V, and W on any Delta drive.