INVT

Home / INVT

INVT Goodrive Fault Codes & Troubleshooting

Technical diagnostic reference for INVT Goodrive (GD) variable frequency inverters, multi-drive systems, solar pump controllers, and DA series AC servo motion drives. Select your model series below to access parameter checks, trip code descriptions, and physical test workflows.

20 Goodrive Inverter Series 1 Hydraulic Servo Series 3 DA Motion Servo Series

INVT Goodrive AC Variable Frequency Drives

20 Models
GD20 →

Economy Mini Vector Inverter for Small Power Applications (0.4 to 110 kW)

GD20-EU →

European Standard Vector Inverter with Built-in STO (Safe Torque Off) SIL3

GD200A →

General Purpose High-Performance Sensorless Vector Inverter (0.75 to 500 kW)

GD350A →

High-End Intelligent Multi-Function Vector Inverter with Custom Expansion Cards

GD350 Series →

High-Performance Vector Inverter Supporting Asynchronous & Synchronous Motors

GD270 →

Specialized Energy-Saving Drive for Fans, Pumps, HVAC & Wastewater Applications

GD10 →

Mini Economy Inverter with Compact DIN-Rail Mounting Design (0.2 to 2.2 kW)

GD18 →

Simple High-Efficiency Micro AC Drive for Basic Conveyors and Packaging Machines

GD100-PV →

Dedicated Solar Water Pump Inverter with Maximum Power Point Tracking (MPPT)

BPD Series →

IP65 High-Protection Solar Water Pump Controller for Harsh Outdoor Environments

GD20-09 Series →

Dedicated High-Performance Variable Frequency Drive for Textile Machinery

GD20-UL Series →

North American Standard cULus Certified Mini Vector Inverter

GD300-01A Series →

Specialized High-Performance Inverter for Rotary Screw Air Compressors

GD300-21 →

Dedicated Inverter System for Single and Multi-Stage Compressors

GD350-19 Series →

Dedicated Crane & Hoisting Vector Inverter with Built-in Mechanical Brake Logic

GD350-UL Series →

cULus Certified Multi-Function Heavy-Duty Vector Inverter Platform

GD600 Series →

Multi-Drive Common DC Bus Inverter System for Continuous Process Plants

GD800 Pro Series →

Heavy Industrial High-Power Modular Inverter for Metallurgy, Mining & Marine

GD800 Series →

Industrial Multi-Drive Modular Platform with Active Front End (AFE) Support

SPC Series →

Solar Pump Booster Controller & PV Hybrid Power Controller Module

INVT Hydraulic Servo Drives

1 Model

INVT DA AC Motion Servo Systems

3 Models

Most Common INVT Goodrive Fault Codes

Diagnostic Quick Reference
Trip Code Trip Description Common Physical Trigger Recommended First Check
OUT1 / OUT2 Inverter Unit Protection Output phase short circuit (U, V, W), grounding short, or internal IGBT module gate failure. Disconnect motor leads and check if drive trips immediately on run command with no motor attached.
OC1 / OC2 Overcurrent (Accel / Decel) Ramp time set too short, sudden mechanical shock load, or motor insulation breakdown. Increase acceleration time (P00.11) or deceleration time (P00.12); inspect motor bearings for drag.
OV1 / OV3 DC Bus Overvoltage Energy generated by motor during deceleration charging internal DC link capacitors above safety trip limit. Extend deceleration time (P00.12), enable overvoltage stall prevention (P08.04), or install dynamic braking resistor.
UV Bus Undervoltage Incoming AC mains line voltage dropped below permissible operating threshold. Check incoming line fuses, measure AC supply voltage across R, S, T terminals, and verify line contactor.
OL1 / OL2 Motor / Inverter Overload Motor or drive operating continuously above rated full load current curve. Check motor rated current setting (P02.01), inspect driven machine for physical blockage, and check ambient temperature.
OH1 / OH2 Inverter Module Overheat Power module heatsink temperature sensor exceeded maximum safety limit. Verify that cooling fan is spinning, clear blocked duct vents, and clean cabinet air intake filters.
ETH1 / ETH2 Grounding Fault (Earth Leakage) Current leakage to ground detected on drive output terminals (U, V, W). Inspect output motor cables for insulation wear or test motor stator windings with a 500V Megohmmeter.
SPI / SPO Input / Output Phase Loss Three-phase input power missing one leg (SPI) or motor output cable disconnected (SPO). Verify line supply continuity and inspect output contactors/motor terminal connections.

How to Clear & Reset INVT Drive Faults

  1. Keypad Reset: Press the red STOP/RST button on the digital LED or LCD keypad.
  2. Digital Input (DI) Terminal Pulse: If hardwired for automation control, pulse the digital input terminal programmed as “Fault Reset” (Function `4` in parameter group P05.01–P05.09).
  3. Communication Control Word: Send reset command `0007H` via Modbus RS-485 / communication fieldbus to register address `2000H`.
  4. Power Cycle: Disconnect incoming 3-phase line power, wait until the keypad display and internal charge LED turn off completely, and restore mains power.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus capacitor voltage measures strictly below 50VDC across terminals [(+)] and [(-)] before opening terminal covers or servicing output terminals U, V, and W on any INVT drive.