INVT Goodrive Fault Codes & Troubleshooting
Technical diagnostic reference for INVT Goodrive (GD) variable frequency inverters, multi-drive systems, solar pump controllers, and DA series AC servo motion drives. Select your model series below to access parameter checks, trip code descriptions, and physical test workflows.
INVT Goodrive AC Variable Frequency Drives
20 ModelsEconomy Mini Vector Inverter for Small Power Applications (0.4 to 110 kW)
European Standard Vector Inverter with Built-in STO (Safe Torque Off) SIL3
General Purpose High-Performance Sensorless Vector Inverter (0.75 to 500 kW)
High-End Intelligent Multi-Function Vector Inverter with Custom Expansion Cards
High-Performance Vector Inverter Supporting Asynchronous & Synchronous Motors
Specialized Energy-Saving Drive for Fans, Pumps, HVAC & Wastewater Applications
Mini Economy Inverter with Compact DIN-Rail Mounting Design (0.2 to 2.2 kW)
Simple High-Efficiency Micro AC Drive for Basic Conveyors and Packaging Machines
Dedicated Solar Water Pump Inverter with Maximum Power Point Tracking (MPPT)
IP65 High-Protection Solar Water Pump Controller for Harsh Outdoor Environments
Dedicated High-Performance Variable Frequency Drive for Textile Machinery
North American Standard cULus Certified Mini Vector Inverter
Specialized High-Performance Inverter for Rotary Screw Air Compressors
Dedicated Inverter System for Single and Multi-Stage Compressors
Dedicated Crane & Hoisting Vector Inverter with Built-in Mechanical Brake Logic
cULus Certified Multi-Function Heavy-Duty Vector Inverter Platform
Multi-Drive Common DC Bus Inverter System for Continuous Process Plants
Heavy Industrial High-Power Modular Inverter for Metallurgy, Mining & Marine
Industrial Multi-Drive Modular Platform with Active Front End (AFE) Support
Solar Pump Booster Controller & PV Hybrid Power Controller Module
INVT Hydraulic Servo Drives
1 ModelINVT DA AC Motion Servo Systems
3 ModelsFlagship High-Performance AC Servo Drive with 23-bit Optical / Magnetic Encoder
Basic Compact Industrial AC Servo Drive for Standard Packaging & Electronics Assembly
Next-Gen High-Dynamic EtherCAT & High-Speed Bus Communication Motion Servo
Most Common INVT Goodrive Fault Codes
Diagnostic Quick Reference| Trip Code | Trip Description | Common Physical Trigger | Recommended First Check |
|---|---|---|---|
| OUT1 / OUT2 | Inverter Unit Protection | Output phase short circuit (U, V, W), grounding short, or internal IGBT module gate failure. | Disconnect motor leads and check if drive trips immediately on run command with no motor attached. |
| OC1 / OC2 | Overcurrent (Accel / Decel) | Ramp time set too short, sudden mechanical shock load, or motor insulation breakdown. | Increase acceleration time (P00.11) or deceleration time (P00.12); inspect motor bearings for drag. |
| OV1 / OV3 | DC Bus Overvoltage | Energy generated by motor during deceleration charging internal DC link capacitors above safety trip limit. | Extend deceleration time (P00.12), enable overvoltage stall prevention (P08.04), or install dynamic braking resistor. |
| UV | Bus Undervoltage | Incoming AC mains line voltage dropped below permissible operating threshold. | Check incoming line fuses, measure AC supply voltage across R, S, T terminals, and verify line contactor. |
| OL1 / OL2 | Motor / Inverter Overload | Motor or drive operating continuously above rated full load current curve. | Check motor rated current setting (P02.01), inspect driven machine for physical blockage, and check ambient temperature. |
| OH1 / OH2 | Inverter Module Overheat | Power module heatsink temperature sensor exceeded maximum safety limit. | Verify that cooling fan is spinning, clear blocked duct vents, and clean cabinet air intake filters. |
| ETH1 / ETH2 | Grounding Fault (Earth Leakage) | Current leakage to ground detected on drive output terminals (U, V, W). | Inspect output motor cables for insulation wear or test motor stator windings with a 500V Megohmmeter. |
| SPI / SPO | Input / Output Phase Loss | Three-phase input power missing one leg (SPI) or motor output cable disconnected (SPO). | Verify line supply continuity and inspect output contactors/motor terminal connections. |
How to Clear & Reset INVT Drive Faults
- Keypad Reset: Press the red STOP/RST button on the digital LED or LCD keypad.
- Digital Input (DI) Terminal Pulse: If hardwired for automation control, pulse the digital input terminal programmed as “Fault Reset” (Function `4` in parameter group P05.01–P05.09).
- Communication Control Word: Send reset command `0007H` via Modbus RS-485 / communication fieldbus to register address `2000H`.
- Power Cycle: Disconnect incoming 3-phase line power, wait until the keypad display and internal charge LED turn off completely, and restore mains power.