Parker

Home / Parker

Parker Hannifin Drives Fault Codes & Troubleshooting

Comprehensive technical diagnostic directory for Parker SSD Drives AC variable frequency inverters, DC590+ digital DC converters, and precision motion servo amplifiers. Select your drive model series below to access parameter checks, trip descriptions, and physical inspection workflows.

13 AC Inverter Series 2 Industrial DC Converters 5 Precision Motion Servos

Parker AC Variable Frequency Drives

13 Models

Parker Industrial DC Drives

2 Models

Parker Motion & Servo Systems

5 Models

Most Common Parker SSD Fault Codes

Diagnostic Quick Reference
Trip Message / Code Legacy Display Trip Name & Nature Recommended First Check
OVERVOLTAGE DCOV / OV DC Bus Overvoltage Extend deceleration ramp time; inspect dynamic braking resistor connections across terminals DC+ and DBR.
DESAT (OVERCURRENT) OC Instantaneous Overcurrent / Desat Output phase short-circuit or IGBT desaturation. Disconnect motor leads and inspect with a 500V Megohmmeter.
UNDERVOLTAGE DCUV / UV DC Bus Undervoltage Mains incoming voltage sagged or phase lost. Measure incoming AC supply line across L1, L2, L3 terminals.
HEATSINK DTRP OH Heatsink Overtemperature Power stack internal temperature sensor exceeded safety limit. Clean heatsink channels and verify cooling fan operation.
MOTOR OVERTEMP OT Motor Thermistor / I²t Trip Motor thermistor circuit (TH1/TH2) open or sustained operation beyond rated motor continuous full load current.
CURRENT LIMIT I-LIM Current Limit Timeout Drive operated at maximum current clamp for longer than allowed stall window. Inspect machine for mechanical jamming.
FIELD OVER I F-OC (DC590+) DC Field Overcurrent DC motor field current exceeded calibrated threshold. Check DC motor shunt field resistance and supply voltage.
SPEED FEEDBACK SPD-ERR Encoder / Tachometer Failure Feedback signal missing or differential encoder channels out of phase. Verify encoder wiring and screening.

How to Clear & Reset Parker SSD Drive Trips

  1. Keypad Reset: Press the red STOP/RESET key on the 6901, 6511, or AC30 graphical operator keypad.
  2. Digital Input Reset: Momentarily pulse the digital terminal configured for “Trip Reset” (Menu: TRIP MANAGEMENT $\rightarrow$ TRIP RESET).
  3. DSE Lite / DSE890 Software: Connect via serial / USB / Ethernet interface, open the online diagnostics window, and click “Acknowledge / Reset Trip”.
  4. Fieldbus Control Word: Set the Trip Reset bit (Bit 7 or manufacturer control word bit) from `0` to `1` via Profinet, Ethernet/IP, or CANopen master PLC.
  5. Power Cycle: Disconnect the incoming 3-phase mains supply, wait until the internal DC bus discharge LED turns off completely, and restore mains power.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus capacitor voltage measures strictly below 50VDC across terminals [DC+] and [DC-] before opening enclosure covers or servicing terminals U, V, and W on any Parker AC or DC drive.