Hitachi Drives Fault Codes & Troubleshooting
Complete diagnostic database for 14 Hitachi drive series. Browse fault codes, trip errors, causes, and step-by-step fixes for industrial AC variable speed frequency inverters. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.
Hitachi AC Variable Frequency Drives
14 ModelsCompact Micro Inverter with Integrated Keypad Potentiometer & Modbus RS485
Dedicated Industrial Fan and Centrifugal Pump Inverter with Energy-Saving Control
Economical Ultra-Compact Machinery Drive Designed for Small OEMs & System Integration
Standard Compact Frequency Inverter for Constant & Variable Torque Machine Tasks
High-Torque Sensorless Vector Micro Drive Delivering 200% Starting Torque at 0.5 Hz
Heavy-Duty Industrial Vector Drive with Closed-Loop Encoder Feedback Capability
Advanced Industrial Vector Inverter with Built-in EzSQ User Programming Logic
General-Purpose Industrial Inverter Engineered for Heavy Machinery & Conveyors
Premium Vector Inverter with Dual Rating Architecture and Dynamic Torque Regulation
Flagship Premium Industrial Inverter with Multi-Protocol Fieldbus & PM Motor Control
High-Performance Sensorless Vector Drive with Integrated Safe Torque Off (STO)
Compact Machinery Inverter Featuring Advanced Motor Auto-Tuning & Energy Savings
Compact Variable Torque Inverter Engineered Specifically for Fans, Pumps & Blowers
Cost-Effective Compact Frequency Drive with Built-in EMC Filter & RoHS Compliance
Most Common Hitachi Drive Fault Codes
Diagnostic Quick Reference| Trip Code | Name / State | Fault Description | Common Root Cause |
|---|---|---|---|
| E01 – E04 | Overcurrent Trip | Instantaneous Overcurrent | Inverter peak current threshold exceeded during constant speed (E01), decel (E02), accel (E03), or other conditions (E04); short circuit or locked rotor. |
| E05 | Overload Trip | Motor Overload Protection | Electronic thermal model tripped due to sustained current exceeding motor rated Full Load Amps (FLA); mechanical jam or undersized motor. |
| E07 | Overvoltage Trip | DC Bus Overvoltage | Intermediate DC link exceeded maximum operating limit; regenerative power during rapid motor deceleration without dynamic braking resistor. |
| E09 | Undervoltage Trip | DC Bus Undervoltage | DC link voltage dropped below allowable limit; utility power sag, loose incoming line terminal connections, or blown input fuse. |
| E14 | Ground Fault | Ground / Earth Fault | Current leakage detected from output motor phases (U, V, W) to earth ground; moisture in motor junction box or damaged cable insulation. |
| E21 | Overheat Trip | Inverter Heatsink Overheat | Internal temperature exceeded safety threshold; clogged ventilation airflow channels, cooling fan failure, or high ambient temperature (>50°C). |
| E12 | External Trip | External Trip Signal (EXT) | The multi-function terminal configured as EXT (External Trip) has been activated by external safety or protective sensors. |
How to Clear & Reset Hitachi Faults
- Keypad Reset: Press the red STOP/RESET key on the front digital operator keypad after correcting the fault root cause.
- Reset Terminal (RS): Send a momentary pulse to the digital input terminal configured for Reset (default multi-function input parameter C001–C007 set to option
18: RS). - ProDriveNext Software: Connect via USB or RS485 Modbus and click the “Trip Reset” command inside Hitachi ProDriveNext software.
- Main Power Cycle: Disconnect the incoming 3-phase AC line power, wait until the internal CHARGE indicator LED completely turns off (minimum 5 minutes), and re-energize the unit.