Nidec Control Techniques Drives Fault Codes & Troubleshooting
Complete diagnostic database for 23 Nidec Control Techniques drive series. Browse fault codes, trip codes, causes, and step-by-step fixes for industrial AC variable speed drives and high-performance servo motion amplifiers. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.
Nidec Control Techniques AC & Industrial Drives
18 ModelsStandard Industrial General Purpose Machinery Inverters with Dual STO Safety
Compact Micro Drive with Integrated NFC Interface & Marshal App Commissioning
Classic Open-Loop Vector Control Component Micro Drive for General Machinery
Proven Compact AC Variable Frequency Inverter with SmartStick Parameter Cloning
Rugged IP66 / NEMA 4X Protected Inverter for Harsh Washdown Environments
Dedicated Building Automation Inverter with Embedded BACnet & Fire Mode Override
Cost-Effective Open and Closed-Loop Sensorless Vector General Purpose Inverters
High-Power Modular Fan, Pump & Compressor Inverter up to 2.8 MW (Modular Power)
Dedicated Water & Wastewater Inverter with Multi-Pump Assist & Pipe Fill Intelligence
High-Speed Frequency Inverter Supporting Up to 3,000 Hz Output Frequency
Ultra-High Speed Inverter for Centrifugal Compressors, Test Benches & Spindles
Value AC Drive for Open-Loop Applications with Fast Parameter Setup
Standard Open-Loop Machinery Drive with Flexible SI Option Module Connectivity
Machinery Open-Loop AC Drive with Dual Integrated Safe Torque Off (SIL3/PLe)
Advanced Open-Loop Inverter with On-Board PLC (CODESYS) & Multi-Line Display
High-Performance Vector Drive with Sensorless Permanent Magnet Motor Control (RFC-S)
Flagship Universal AC & Servo Drive with Real-Time Ethernet & Advanced Motion Control
Legendary Universal Industrial Inverter Platform Supporting AC Induction & Servo Motors
Digitax AC Servo Drives & Motion Systems
5 ModelsHigh-Density Compact Servo Drive for Centralized Multi-Axis Motion via Option Modules
High-Speed Real-Time EtherCAT Dynamic Servo Drive with Dual Safe Torque Off
Standalone Machine Motion Controller & Servo Drive with On-Board High-Speed Processor
Cost-Effective Compact Pulse & Analog Directional Motion Servo Amplifier System
Classic Modular Dynamic Servo Drive (Base, Indexer, Plus & EZ-Motion Architectures)
Most Common Control Techniques Trip Codes
Diagnostic Quick Reference| Trip String | Trip No. | Trip Description | Common Root Cause |
|---|---|---|---|
| OI.AC | 1 | Instantaneous Output Overcurrent | Peak instantaneous current limit exceeded; short circuit across motor terminals (U, V, W), jammed mechanism, or high motor inertia. |
| OV | 2 | DC Bus Overvoltage | Intermediate DC bus voltage exceeded trip threshold; rapid deceleration without braking resistor, or defective braking transistor. |
| UU | 3 | DC Bus Undervoltage | DC link voltage dropped below operating threshold; mains power interruption, blown incoming branch fuse, or severe AC voltage sag. |
| OI.SC | 8 | Drive Output Short Circuit | Direct low-impedance short circuit detected at inverter motor output or earth leakage; verify phase-to-phase and phase-to-ground resistance. |
| It.AC | 6 | Inverter Thermal Overload (I²t) | Continuous current exceeded drive rated capacity over time; inspect mechanical binding or improper motor nameplate configuration. |
| OHt.Inverter | 21 | Heatsink Over-Temperature | Heatsink or power module temperature sensor exceeded trip limit; blocked airflow louvers, failing cooling fan, or high enclosure ambient (>50°C). |
| PH.Lo | 32 | Input Phase Loss | High DC link voltage ripple detected due to an open phase on the AC line power supply or an unseated disconnect switch contact. |
How to Clear & Reset Control Techniques Trips
- Keypad Reset: Press the red STOP / RESET key directly on the front-mounted keypad or remote CI-Keypad.
- Digital Input Terminal: Apply a momentary 24VDC pulse to the digital input configured for drive reset (default Terminal T5 or parameter Pr 10.038 / Pr 10.38).
- Connect / Machine Control Studio Software: Connect via USB (CT Comms Cable) or Ethernet and click the “Reset Drive” button on the dashboard toolbar.
- Power Disconnect Cycle: Remove main 3-phase AC power, wait 5 minutes until the display goes completely blank and DC bus capacitors fully discharge, and restore power.