LS Electric Drives Fault Codes & Troubleshooting

Comprehensive technical diagnostic directory for LS Electric (formerly LG Industrial Systems / LSIS) variable frequency inverters and L7 motion servo drives. Select your model series below to access parameter checks, trip code descriptions, and physical inspection workflows.

11 AC Inverter Series 5 Servo & Motion Systems Sensorless & Flux Vector

LS Electric General Purpose & Industrial Inverters

11 Models

LS Electric L7 & iX7 AC Servo Systems

5 Models

Most Common LS Electric Inverter Fault Codes

Diagnostic Quick Reference
Trip Code Trip Name Common Physical Trigger Recommended First Check
OCT / OC2 Overcurrent Trip Inverter output current exceeded 200% of rated value due to short accel time, motor short, or jammed load. Increase acceleration ramp time (ACC parameter) and measure motor winding resistance with wires disconnected.
OVT Overvoltage Trip Motor regenerative energy during rapid deceleration charging the internal DC bus above safety limit (400V/800V). Extend deceleration ramp time (dEC parameter) and verify dynamic braking unit and resistor connections.
GFT Ground Fault Trip Current leakage to protective earth ground detected at inverter output terminals (U, V, W). Check motor terminal box for moisture/carbon build-up and perform an insulation resistance test with a 500V Megger.
LVT / LUT Low Voltage Trip Main DC bus voltage dropped below minimum operating limit due to incoming line drop or power interruption. Check incoming AC mains line voltage across R, S, T terminals and inspect main magnetic contactor contacts.
OHT Overheat Trip Inverter power module heatsink temperature exceeded allowable threshold. Verify cooling fan operation, clear blocked ventilation channels, and replace clogged enclosure intake filters.
POT Output Phase Loss One or more output phases (U, V, W) disconnected or drawing unbalanced motor current. Check output motor cable terminal screws and inspect any intermediate motor disconnect switches.
OLT / ETH Overload / Electronic Thermal Continuous motor current exceeded thermal rating curve for longer than allowed time limit. Check motor rated current setting (in motor parameter group) and verify driven machine mechanical load.
EXT / BX External Trip / Base Block External interlock trip signal received on programmed digital input terminal or emergency stop activated. Inspect safety switches wired to digital inputs and check external interlock relay logic.

How to Clear & Reset LS Electric Inverter Faults

  1. Keypad Reset: Press the red STOP/RESET button on the front 7-segment display or LCD loader.
  2. Digital Input Reset: Momentarily pulse the digital input terminal assigned to “RST” (Trip Reset) (Configured in Input Terminal parameters, e.g., `In.65`~`In.72` set to `14`).
  3. DriveView Software: Connect via RS-485 / USB, open DriveView 7 or DriveView 9, and click the “Reset” button on the status monitoring panel.
  4. Power Cycle: Disconnect main AC line power, wait until the keypad display and internal charge LED turn off completely (discharge of internal capacitors), and restore line power.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus capacitor voltage measures strictly below 50VDC across terminals [P1(+)] and [N(-)] before opening enclosure covers or servicing terminals U, V, and W on any LS Electric drive.