LS Electric Drives Fault Codes & Troubleshooting
Comprehensive technical diagnostic directory for LS Electric (formerly LG Industrial Systems / LSIS) variable frequency inverters and L7 motion servo drives. Select your model series below to access parameter checks, trip code descriptions, and physical inspection workflows.
LS Electric General Purpose & Industrial Inverters
11 ModelsStandard General Purpose Drive with Enhanced Sensorless Vector Control (0.4 to 22 kW)
High-Performance Powerful Compact Inverter (Side-by-Side Installation & IP66 Options)
Classic Compact Sensorless Vector Inverter with Built-in Dynamic Braking Transistor
Dedicated Fan, Pump, and HVAC Inverter with Multi-Motor Scheduling & Soft Fill Logic
Heavy Duty High-Precision Vector Inverter with Graphic LCD & Synchro-PM Motor Control
Dedicated High-Capacity Fan & Pump Inverter with Dual Rating (5.5 to 450 kW)
Cost-Effective Compact Micro Drive for Small Conveyors, Fans & Packaging Machinery
Single-Phase Input Compact Sensorless Vector Inverter with Integrated Potentiometer
Micro Inverter with Ultra-Small Footprint for Fractional Horsepower Applications
High-Precision Full Flux Vector Inverter for Cranes, Elevators, Hoists & Winders
Dedicated Elevator & Passenger Lift Inverter with Specialized Anti-Rollback Algorithms
LS Electric L7 & iX7 AC Servo Systems
5 ModelsEtherCAT High-Dynamic Motion Servo Drive with 20-Bit BiSS-C Serial Encoder Interface
Pulse-Train & Standalone Point-to-Point Position Indexing AC Servo Drive
Standard Multi-Function Pulse / Analog Velocity AC Servo Drive Package
Compact Cost-Effective Servo Drive for Automated Pick-and-Place & Assembly Tools
Next-Gen Multi-Axis EtherCAT Synchronous Motion Servo System (High Speed 100 Mbps)
Most Common LS Electric Inverter Fault Codes
Diagnostic Quick Reference| Trip Code | Trip Name | Common Physical Trigger | Recommended First Check |
|---|---|---|---|
| OCT / OC2 | Overcurrent Trip | Inverter output current exceeded 200% of rated value due to short accel time, motor short, or jammed load. | Increase acceleration ramp time (ACC parameter) and measure motor winding resistance with wires disconnected. |
| OVT | Overvoltage Trip | Motor regenerative energy during rapid deceleration charging the internal DC bus above safety limit (400V/800V). | Extend deceleration ramp time (dEC parameter) and verify dynamic braking unit and resistor connections. |
| GFT | Ground Fault Trip | Current leakage to protective earth ground detected at inverter output terminals (U, V, W). | Check motor terminal box for moisture/carbon build-up and perform an insulation resistance test with a 500V Megger. |
| LVT / LUT | Low Voltage Trip | Main DC bus voltage dropped below minimum operating limit due to incoming line drop or power interruption. | Check incoming AC mains line voltage across R, S, T terminals and inspect main magnetic contactor contacts. |
| OHT | Overheat Trip | Inverter power module heatsink temperature exceeded allowable threshold. | Verify cooling fan operation, clear blocked ventilation channels, and replace clogged enclosure intake filters. |
| POT | Output Phase Loss | One or more output phases (U, V, W) disconnected or drawing unbalanced motor current. | Check output motor cable terminal screws and inspect any intermediate motor disconnect switches. |
| OLT / ETH | Overload / Electronic Thermal | Continuous motor current exceeded thermal rating curve for longer than allowed time limit. | Check motor rated current setting (in motor parameter group) and verify driven machine mechanical load. |
| EXT / BX | External Trip / Base Block | External interlock trip signal received on programmed digital input terminal or emergency stop activated. | Inspect safety switches wired to digital inputs and check external interlock relay logic. |
How to Clear & Reset LS Electric Inverter Faults
- Keypad Reset: Press the red STOP/RESET button on the front 7-segment display or LCD loader.
- Digital Input Reset: Momentarily pulse the digital input terminal assigned to “RST” (Trip Reset) (Configured in Input Terminal parameters, e.g., `In.65`~`In.72` set to `14`).
- DriveView Software: Connect via RS-485 / USB, open DriveView 7 or DriveView 9, and click the “Reset” button on the status monitoring panel.
- Power Cycle: Disconnect main AC line power, wait until the keypad display and internal charge LED turn off completely (discharge of internal capacitors), and restore line power.