WEG Drives Fault Codes & Troubleshooting
Complete diagnostic database for 13 WEG drive series (CFW, ADV & ADL series). Browse fault codes, alarms, causes, and step-by-step fixes for industrial AC variable speed drives, HVAC inverters, and lift controllers. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.
WEG CFW Series AC Variable Frequency Drives
10 ModelsCompact Micro Inverter with Vectrue Sensorless Vector Technology for General Machinery
High-Performance Modular System Drive with Multi-Pump Control & Plug-and-Play Slots
Ultra-Compact Micro VFD with Built-in SoftPLC for Small Machinery & Solar Pumping
Heavy Industrial Vector Inverter Featuring High Dynamic Torque & Independent Ramp Control
Economical Component Micro Drive for Basic Single and Three-Phase Motor Speed Control
Flexible Machinery Inverter with Built-in SoftPLC, Flash Memory & Expansion Modules
Advanced Machinery Drive with Modular Plug-in Communication, I/O & Integrated STO
Dedicated HVAC & Building Automation Inverter with Built-in BACnet & Fire Mode Override
Energy-Optimized HVAC and Water Pumping Inverter with Advanced Multiplex Cascade Control
Next-Generation Industrial Drive Platform with Embedded IoT, High Efficiency & Color Display
WEG Industrial & Elevator Drives
3 ModelsSpecialized Elevator & Lift Inverter for Geared & Gearless Traction Synchronous Motors
Specialized High-Response Servo Pump Inverter for Plastic Injection Molding Machines
Field-Oriented Vector Industrial Drive for Heavy-Duty System Automation & Metal Processing
Most Common WEG Drive Fault Codes
Diagnostic Quick Reference| Fault Code | Alarm Code | Fault Description | Common Root Cause |
|---|---|---|---|
| F0070 / F0071 | A0046 | Overcurrent / Short Circuit | Output current exceeded peak allowable limit; phase-to-phase short on U, V, W, jammed mechanical load, or rapid acceleration ramp. |
| F0022 | A0022 | DC Bus Overvoltage | DC link voltage exceeded upper threshold; high regenerative energy returned during deceleration ramp without dynamic braking resistor. |
| F0006 | A0006 | DC Bus Undervoltage | Intermediate DC link voltage dropped below operating limit; mains supply failure, severe line voltage sag, or open pre-charge relay. |
| F0072 | A0072 | Ground / Earth Fault | Ground leakage current detected at motor output phases; damaged motor power cable jacket or deteriorated stator insulation. |
| F0078 | A0047 | Motor Overload (I²t) | Continuous operation exceeding motor nameplate Full Load Amps (FLA) according to electronic thermal model; mechanical binding. |
| F0080 / F0081 | A0050 | Heatsink Overtemperature | IGBT module or heatsink temperature sensor exceeded safety threshold; clogged ventilation ducts, fan failure, or high ambient (>50°C). |
| F0030 | A0030 | Input Phase Loss | Missing phase or high DC bus ripple detected on incoming 3-phase line terminals (L/L1, N/L2, L3) or blown line-side fuse. |
How to Clear & Reset WEG Faults
- HMI Keypad Reset: Press the red O / RESET key directly on the front-mounted HMI keypad after addressing the fault root cause.
- Digital Input (DI) Terminal: Apply a momentary 24VDC pulse to the digital input configured for Reset (e.g., parameter P0263–P0270 set to option
Reset). - SuperDrive G2 / WPS Software: Connect via USB or fieldbus, open the diagnostic status window inside WEG SuperDrive G2 or WPS (WEG Programming Suite), and click “Reset Fault”.
- Main Power Disconnect Cycle: Turn off incoming 3-phase AC line power, wait until the internal DC bus charge LED completely turns off and voltage drops below 50VDC (minimum 5 minutes), and reapply power.