Danfoss Drives Fault Codes & Troubleshooting
Complete diagnostic database for 23 Danfoss & VACON drive series. Browse fault codes, alarms, causes, and step-by-step fixes for AC & servo drives. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.
VLT Series AC Drives
8 ModelsCompact General Purpose OEM Drive with Coated PCBs & PI Controller
Heavy Duty Automation Drive for High-Demand Asynchronous & PM Motors
Dedicated Industrial Automation Drive for Machine Builders and OEMs
Dedicated Building Automation & Fan/Chiller Control Inverter
Specialized Inverter for Refrigeration Compressors, Condensers & Pumps
Advanced Water & Wastewater Drive with Integrated Cascade Controller
Flexible Machinery Drive with Integrated Safe Torque Off (STO) & DC Choke
VLT HVAC Basic Drive for Essential Fan and Centrifugal Pump Control
VACON Series Drives
5 ModelsCompact Machinery Inverter with Built-in PLC Functionality (IEC 61131-3)
Dedicated Flow Control Drive for Intelligent Water, Fan & Compressor Systems
Multipurpose Industrial Drive with Integrated Ethernet & Motor Control Features
Slim Enclosure Drive for Harsh Conditions with Passive Cooling Design
Heavy Industrial High-Power Drive for Dynamic Motion & Closed-Loop Vector
Legacy & Specialty Drives
9 ModelsClassic Compact Production Drive with Cold-Plate Heat Dissipation Options
Legacy Industrial Drive Series Known for Robust Analog & Digital Regulation
Classic HVAC Dedicated Controller for Retrofit Plant Infrastructure
High-Precision Flux Vector Legacy Drive with Synchronization Cards
Dedicated HVAC Legacy Inverter Engineered for Variable Torque Pump Loads
Specialized Aqua & Municipal Wastewater Treatment Inverter Architecture
Standard Ultra-Compact Micro Frequency Converter for Machinery
Rugged Decentralized IP66 / NEMA 4X Outdoor Enclosure Drive
Heavy-Duty Motor-Mountable Decentralized Inverter for Extreme Environments
Servo & Motion Drives
1 ModelMost Common Danfoss & VACON Drive Fault Codes
Diagnostic Quick Reference| Danfoss Alarm | VACON Code | Fault Name | Common Root Cause |
|---|---|---|---|
| Alarm 13 | F1 | Overcurrent | Drive peak current limit exceeded due to motor short circuit, mechanical binding, or abrupt acceleration ramp. |
| Alarm 7 | F2 | DC Link Overvoltage | Regenerative kinetic energy fed back during motor deceleration; verify ramp-down time or braking resistor circuit. |
| Alarm 8 | F9 | DC Link Undervoltage | Line voltage dip, open circuit on incoming mains supply, or damaged intermediate pre-charge contactor. |
| Alarm 14 | F3 | Ground / Earth Fault | Current leakage from motor phases to earth; inspect motor cable shielding, terminal dampness, or stator insulation. |
| Alarm 9 | F11 | Inverter Overload | Continuous operation exceeding 100% rated thermal capacity; verify load sizing and parameter group 14 derating. |
| Alarm 4 | F10 | Mains Phase Loss | Missing phase, blown line-side fuse, or severe phase supply imbalance (>3%) on incoming terminals L1, L2, L3. |
How to Clear & Reset Danfoss & VACON Faults
- LCP Keypad Reset: Press the yellow or red [Reset] key directly on the Local Control Panel (or [Back/Reset] on VACON keypads).
- Digital Input Pulse: Send a 24VDC pulse to the digital input configured for Reset (default Terminal 27 or Terminal 19, Parameter
5-1x). - Setup Software Interface: Connect via USB or Fieldbus and trigger the fault acknowledge button inside Danfoss MCT 10 or VACON Live.
- Mains Power Cycle: Power down the 3-phase line supply, wait until the control panel display goes completely blank (minimum 4–15 minutes depending on frame size), and reapply power.